Products

The offer of pre-insulated steel pipes includes a complete range of pipes, fittings and pre-insulated fittings for the transmission of heating medium and hot utility water. Pipes are supplied in a wide range of carrier pipe diameters – in the case of a single pipe from DN 20 mm to DN 1200 mm, and in the case of a double pipe from DN 20 mm to DN 200 mm. For underground heating networks, a PEHD high-density polyethylene pipe is used as a casing pipe; for overhead heating networks, pipes are made in casing made of rolled sheets (SPIRO type). Pre-insulated pipes can be equipped with a polyurethane insulation moisture detection system.

• Pipes manufactured in accordance with PN-EN 253, PN-EN 448, PN EN 489, PN-EN 13941,

• A wide range of pipe operating temperatures up to max. + 152 ° C,

• Complex construction of pipes,

• Ready pre-insulated elements (elbows, tees, valves),

• Leak detection systems (impulse or brandes),

• Low PUR foam insulation coefficient λ = max. 0.029 (W / mK),

• Long installation life

Single pre-insulated steel pipe dn200-dn700

Product not available in the e-shop

SINGLE PRE-INSULATED STEEL PIPE DN200-DN700

Liczba szt.

Pipes intended for transmission of heating medium and hot domestic water.

The pipes are manufactured in lengths of 6 and 12 meters. Pre-insulated pipes can be equipped with a polyurethane insulation moisture detection system. The standard solution is the impulse leak detection system. On special request, the BRANDES system, HDW system or other system can also be used, according to individual customer needs.

  • Pipes manufactured in accordance with PN-EN 253, PN-EN 448, PN EN 489, PN-EN 13941
  • A wide range of pipe operating temperatures up to max. + 152 ° C
  • Complex construction of pipes
  • Ready-made pre-insulated elements (elbows, tees, valves)
  • Leak detection systems (impulse or Brandes)
  • Low insulation coefficient of PUR foam λ=max. 0.029 (W/mK)
  • Long service life of the installation

Pre-insulated pipe construction

  • inner duct pipe made of steel
  • thermal insulation is made of rigid polyurethane foam, evenly filling the space between the duct pipe and the casing pipe. The vapour generating agent is cyclopentane
  • casing pipe made of high-density polyethylene PEHD
Black or galvanized steel pipe, DN mm 200 250 300 350 400 450 500 600 700
PEHD casing pipe DN 315 400 450 500 520 560 630 800 900
Steel pipe outer diameter mm 219,1 273 323,9 355,6 406,4 457 508 610 711
Commercial length mm 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12
Black steel pipe (zs) / (bs) pcs zs/bs zs/bs zs zs zs zs zs zs zs
90 ° bend - black pipe (zs) / (bs) 1.00 x 1.00 m for DN 250, 1.50 x 1.50 m from DN 300 pcs zs/bs zs/bs zs zs zs zs zs zs zs
90 ° elbow - black pipe (zs) / bs) 1.00 x 2.00 m for DN 200, 1.20 x 2.00 m for DN 250 pcs zs/bs zs/bs - - - - - - -
Fixed point L-2.5 m pcs zs/bs zs/bs zs/bs - - - - - -
TP (zs) / (bs) flat tee or TW (zs) / (bs) rising tee pcs TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW
Joint assembly (heat shrink sleeve, bands heat-shrinkable, PUR foams, plugs) type NT kpl. NT NT NT - - - - - -
Radiation cross-linked heat shrinkable joint NTX (glue + mastic) kpl. NTX NTX - - - - - - -
Pre-insulated black (zs) / (bs) shut-off ball valve ZK (complete with casing pipe, key, street box) kpl. ZK ZK - - - - - - -
Pre-insulated black (zs) / (bs) shut-off ball valve with drainage and venting ZKOD kpl. ZKOD ZKOD - - - - - - -
Pre-insulated black (zs) / (bs) shut-off ball valve with one ZKD vent valve or one ZKO drain valve kpl. ZKD/ZKO ZKD/ZKO - - - - - - -
Pre-insulated black ball valve (zs) / (bs), venting ZD or drainage ZO kpl. ZD/ZO ZD/ZO - - - - - - -
Black pre-insulated venturi Z (zs) / (bs) (one dimension difference) pcs zs/bs zs/bs - - - - - - -
Electrically welded DX joint assembly pcs DX DX DX DX DX DX DX DX DX
Passage through the wall - rubber damper P pcs P P P P P P P P P
End-Cap isolation pcs + + + - - - - - -