Products

The offer of pre-insulated steel pipes includes a complete range of pipes, fittings and pre-insulated fittings for the transmission of heating medium and hot utility water. Pipes are supplied in a wide range of carrier pipe diameters – in the case of a single pipe from DN 20 mm to DN 1200 mm, and in the case of a double pipe from DN 20 mm to DN 200 mm. For underground heating networks, a PEHD high-density polyethylene pipe is used as a casing pipe; for overhead heating networks, pipes are made in casing made of rolled sheets (SPIRO type). Pre-insulated pipes can be equipped with a polyurethane insulation moisture detection system.

• Pipes manufactured in accordance with PN-EN 253, PN-EN 448, PN EN 489, PN-EN 13941,

• A wide range of pipe operating temperatures up to max. + 152 ° C,

• Complex construction of pipes,

• Ready pre-insulated elements (elbows, tees, valves),

• Leak detection systems (impulse or brandes),

• Low PUR foam insulation coefficient λ = max. 0.029 (W / mK),

• Long installation life

Double pre-insulated steel pipe

Product not available in the e-shop

DOUBLE PRE-INSULATED STEEL PIPE

Liczba szt.

Pipes intended for transmission of heating medium and hot domestic water.

The pipes are manufactured in lengths of 6 and 12 meters. Pre-insulated pipes can be equipped with a polyurethane insulation moisture detection system. The standard solution is the impulse leak detection system. On special request, the BRANDES system, HDW system or other system can also be used, according to individual customer needs.

The offer of pre-insulated steel pipes includes a complete range of pipes, fittings and pre-insulated fittings for the transmission of heating medium and hot domestic water. The pipes are supplied in a wide range of duct pipe diameters – in the case of a single pipe from DN 20 mm to DN 1200 mm, and in the case of a double pipe from DN 20 mm to DN 200 mm. For underground heating networks, a PEHD high-density polyethylene pipe is used as a casing pipe; for overhead heating networks, pipes are made in casing made of rolled sheets (SPIRO type). Pre-insulated pipes can be equipped with a polyurethane insulation moisture detection system.

  • Pipes manufactured in accordance with PN-EN 253, PN-EN 448, PN EN 489, PN-EN 13941
  • A wide range of pipe operating temperatures up to max. +152°C
  • Complex construction of pipes
  • Ready pre-insulated elements (elbows, tees, valves)
  • Leak detection systems (impulse or Brandes)
  • Low insulation coefficient of PUR foam λ=max. 0.029 (W/mK)
  • Long service life of the installation

Pre-insulated pipe construction

  • inner duct pipe made of steel
  • thermal insulation is made of rigid polyurethane foam, evenly filling the space between the duct pipe and the casing pipe. The vapour generating agent is cyclopentane
  • casing pipe made of high-density polyethylene PEHD
Black steel pipe DN mm 20 25 32 40 50 65 80 100 125 150
PEHD casing pipe DN 125 140 160 160 200 225 250 315 400 450
Steel pipe outer diameter mm 26,9 33,7 42,4 48,3 60,3 76,1 88,9 114,3 139,7 168,3
Commercial length m 6 6 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12 6 ; 12
Double pre-insulated steel pipe (zs) / (bs) szt. zs/bs zs/bs zs/bs zs/bs zs/bs zs/bs zs/bs zs/bs zs/bs zs/bs
90 ° bend - black pipe 1.00 x 1.00 m szt. + + + + + + + + + +
90 ° bend - black pipe 1.00 x 2.00 m szt. + + + + + + + + - -
TP (zs) / (bs) flat tee or TW (zs) / (bs) rising tee szt. TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW TP/TW
Joint assembly (heat shrink sleeve, bands heat-shrinkable, PUR foams, plugs) type NT kpl. NT NT NT NT NT NT NT NT NT NT
Radiation cross-linked heat shrinkable joint NTX (glue + mastic) kpl. NTX NTX NTX NTX NTX NTX NTX NTX NTX -
ZK black pre-insulated shut-off ball valve (including a casing pipe, key, street box) kpl. ZK ZK ZK ZK ZK ZK ZK ZK - -
Pre-insulated black (zs) / (bs) shut-off ball valve with drainage and venting ZKOD kpl. - - - ZKOD ZKOD ZKOD ZKOD ZKOD - -
Pre-insulated black (zs) / (bs) shut-off ball valve with one ZKD vent valve or one ZKO drain valve kpl. - ZKD/ZKO ZKD/ZKO ZKD/ZKO ZKD/ZKO ZKD/ZKO ZKD/ZKO ZKD/ZKO - -
Pre-insulated black ball valve (zs) / (bs) venting ZD kpl. - ZD ZD ZD ZD ZD ZD ZD - -
Pre-insulated black ball valve (zs) / (bs) for drainage ZO kpl. - - - ZO ZO ZO ZO ZO - -
Black preinsulated venturi Z (zs) / (bs) (difference of one dimensions) szt. - Z Z Z Z Z Z Z - -
Passage through the wall - rubber damper P szt. P P P P P P P P P P
End-Cap isolation szt. + + + + + + + + - -